Eaton CH generator interlock kit

The kit
CHMIKCSR, CHPMIKCH or CHPMIKCSR
The kit depends on the main breaker. The generator breaker is a CHF230 for a 30 A generator or a CHF250 for a 50 A one.

An interlock is a plate on the panel's cover that lets either the main breaker or the generator breaker be on, never both, so a portable generator can feed the house without sending power back into the utility's lines. Each kit is made for one panel line and one kind of main breaker. The label inside the panel door names the maker and the panel's catalog number, and the main breaker's type is printed on the breaker itself. CH breakers are 3/4 inch wide per pole, with a trip flag and tan handles on most. Eaton's BR breakers are wider and do not fit a CH panel.

By main breaker

KitMain breakerFits
CHMIKCSRCSR or CSH main breakerCH panels with a CSR or CSH main
Standard neutral bar
CHPMIKCHBackfed CH main breakerCH plug-on neutral panels with a backfed main
Plug-on neutral rail
CHPMIKCSRCSR main breakerCH plug-on neutral panels with a CSR main
Plug-on neutral rail

For any other CH panel, the label inside the door names the kit if Eaton makes one.

Generator breaker, inlet and cord

The generator breaker is a standard two-pole breaker from the panel's own line, fed backward from the generator. Its size follows the generator's 240 V outlet.

Generator outletUp toBreakerCopper wireInletCord
L14-307,200 WCHF230
30 A
10 AWGL14-30 inletL14-30P to L14-30R
14-50 or CS636912,000 WCHF250
50 A
8 AWG, or 6 AWG NM cableCS6375 inlet14-50P or CS6364 to CS6365

Watts are the outlet's limit at 240 V; the generator's own running rating may be lower. Wire sizes are from NEC Table 310.16: the 75°C column for wire in conduit and the 60°C column for NM cable.

Before buying

Where to buy

The links search Amazon for each part number. Check that the listing shows the same number before buying.

The interlock kit

Eaton CHMIKCSRUp to 225 A · CH panels with a CSR or CSH main · Interlock kitCSR or CSH main breaker. Standard neutral bar View on Amazon
Eaton CHPMIKCH125 A · CH plug-on neutral panels with a backfed main · Interlock kitBackfed CH main breaker. Plug-on neutral rail View on Amazon
Eaton CHPMIKCSRUp to 225 A · CH plug-on neutral panels with a CSR main · Interlock kitCSR main breaker. Plug-on neutral rail View on Amazon

The generator breaker

Eaton CHF23030 A · Eaton CH panels · Generator with an L14-30 outlet30 A two-pole, backfed as the generator breaker; needs a hold-down View on Amazon
Eaton CHF25050 A · Eaton CH panels · Generator with a 14-50 or CS6369 outlet50 A two-pole, backfed as the generator breaker; needs a hold-down View on Amazon

Inlet and cord

L14-30 power inlet box30 A · Any panel · Outside wallTakes the cord from a generator with an L14-30 outlet View on Amazon
L14-30 generator cord30 A · Any panel · Generator to inletL14-30P plug to L14-30R connector View on Amazon
CS6375 50 amp power inlet box50 A · Any panel · Outside wallTakes the cord from a generator with a 50 A outlet View on Amazon
CS6364 to CS6365 50 amp generator cord50 A · Any panel · Generator to inletFor a generator with a CS6369 outlet View on Amazon
14-50P to CS6365 50 amp generator cord50 A · Any panel · Generator to inletFor a generator with a 14-50 outlet View on Amazon

Other makers' kits

Generator interlock kit for Eaton CHSee listing · Eaton CH panels · Interlock kitPlates from other makers, each for named panel models. Check that the listing names the catalog number on your panel's label View on Amazon

As an Amazon Associate we earn from qualifying purchases.

Common questions

Which generator interlock kit fits an Eaton CH panel?
It depends on the main breaker: the CHMIKCSR for CH panels with a CSR or CSH main (CSR or CSH main breaker); the CHPMIKCH for CH plug-on neutral panels with a backfed main (backfed CH main breaker); the CHPMIKCSR for CH plug-on neutral panels with a CSR main (CSR main breaker). For any other CH panel, the label inside the door names the kit if Eaton makes one. The kit has to be one the panel is listed for.
What is the generator breaker in an Eaton CH panel?
A CHF230 for a generator with an L14-30 outlet, wired with 10 AWG copper wire, or a CHF250 for one with a 14-50 or CS6369 outlet, wired with 8 AWG copper wire in conduit or 6 AWG NM cable. It is fed from the generator rather than the panel, so section 408.36(D) of the National Electrical Code requires a hold-down that keeps it from being pulled off.
Is a generator interlock kit up to code?
Yes, when it is listed for the panel. Section 702.5 of the National Electrical Code requires transfer equipment for a generator that feeds a house, so it cannot send power back into the utility's lines, and an interlock does that by keeping the main and generator breakers from being on together. Most places require a permit, and some inspectors accept only the panel maker's kit.
Can a portable generator run an EV charger through an interlock?
Rarely. A charger set to 40 A draws 9,600 W, more than an L14-30 generator outlet supplies (7,200 W), and most of what a 50 A outlet supplies (12,000 W) before the house's own loads. Switch the charger's breaker off while on generator power, or turn the charger's current down if the generator has room to spare.

Other panels

Kit numbers are from Eaton's CHMIKCSR page, CHPMIKCH page and CHPMIKCSR page. Code references are to the National Electrical Code. Local rules differ, so have a licensed electrician confirm the kit, breaker and wire before work starts. Updated November 13, 2026.