Eaton CH breaker for an EV charger
These fit Eaton CH panels. The label inside the panel door names the maker and lists the breakers the panel accepts, so check it first. CH breakers are 3/4 inch wide per pole, with a trip flag and tan handles on most. Eaton's BR breakers are wider and do not fit a CH panel.
By charger
A charger may draw 80% of its breaker's rating, so each charger setting needs the breaker below. A charger that plugs into an outlet needs the GFCI version; a hardwired one usually takes the standard version.
| Charger set to | Breakerand wire | Plugs into an outlet | Hardwired |
|---|---|---|---|
| 16 A | 20 A12 AWG | CH220GFT or CHN220GF a 6-20 outlet |
CHF220 |
| 24 A | 30 A10 AWG | CH230GFT or CHN230GF a 14-30 or 6-30 outlet |
CHF230 |
| 32 A | 40 A8 AWG | CH240GFT or CHN240GF a 6-50 or 14-50 outlet on a 40 A circuit |
CHF240 |
| 40 A | 50 A8 AWG, or 6 AWG NM cable | CH250GFT or CHN250GF a 14-50 or 6-50 outlet |
CHF250 |
| 48 A | 60 A6 AWG, or 4 AWG NM cable | No common outlet; hardwire it | CHP260 |
Every breaker here is two-pole, 120/240 V. Wire sizes are from NEC Table 310.16: the 75°C column for wire in conduit and the 60°C column for NM cable. A long run may need a size larger. The second GFCI number is the plug-on neutral version.
Outlet or hardwired
- An outlet needs GFCI. Section 625.54 of the 2020 and 2023 code requires ground-fault protection on any outlet installed for EV charging, and at 240 V that means a GFCI breaker. The charger's own protection and the breaker's can trip each other; the outlet or hardwired guide covers that trade.
- The pigtail. The CH250GFT has a coiled white wire that goes to the panel's neutral bar, even for a 6-50 outlet, which has no neutral wire of its own; the breaker's electronics need it. A panel with a plug-on neutral rail can take the CHN250GF instead, which clips onto the rail.
- Hardwired. The outlet rule does not apply, and most hardwired chargers have ground-fault protection built in, so the standard breaker is usual. Tesla's manual says the Wall Connector needs no additional GFCI. Outdoors, section 210.8(F) can call for GFCI on a circuit of 50 A or less.
- 48 A needs hardwiring. It takes a 60 A breaker, and a 60 A circuit has no common outlet. Only a car that accepts more than 40 A gains from it; see 40 A or 48 A.
Before buying
- Two spaces. A two-pole breaker takes two spaces next to each other in the panel.
- Room on the service. A 50 A or 60 A circuit can overload a small service. The 100 A panel guide covers the load calculation.
- Match the label. Use a breaker type the panel's label lists. One from another line can look like it fits without being listed for that panel.
- A permit. Most places require a permit for a new circuit, and many require a licensed electrician to do the work.
- Generator backup. The Eaton CH generator interlock page has the kit that lets a portable generator feed this panel, with its breaker, inlet and cord.
Where to buy
The links search Amazon for each part number. Check that the listing shows the same number before buying.
For a charger that plugs into an outlet
| Eaton CH250GFT50 A · Eaton CH panels · 14-50 or 6-50 outlet50 A two-pole GFCI, self-testing, with a pigtail neutral | View on Amazon |
| Eaton CH240GFT40 A · Eaton CH panels · 14-50 or 6-50 outlet, 40 A circuit40 A two-pole GFCI, self-testing, with a pigtail neutral | View on Amazon |
| Eaton CH230GFT30 A · Eaton CH panels · 14-30 or 6-30 outlet30 A two-pole GFCI, self-testing, with a pigtail neutral | View on Amazon |
| Eaton CH220GFT20 A · Eaton CH panels · 6-20 outlet20 A two-pole GFCI, self-testing, with a pigtail neutral | View on Amazon |
GFCI, for a panel with a plug-on neutral rail
| Eaton CHN250GF50 A · Eaton CH panels · 14-50 or 6-50 outlet50 A two-pole GFCI, plug-on neutral | View on Amazon |
| Eaton CHN240GF40 A · Eaton CH panels · 14-50 or 6-50 outlet, 40 A circuit40 A two-pole GFCI, plug-on neutral | View on Amazon |
For a hardwired charger
| Eaton CHP26060 A · Eaton CH panels · Hardwired charger60 A two-pole, standard. Eaton's 60 A CH breaker is the CHP260; the CHF line stops at 50 A. | View on Amazon |
| Eaton CHF25050 A · Eaton CH panels · Hardwired charger50 A two-pole, standard | View on Amazon |
| Eaton CHF24040 A · Eaton CH panels · Hardwired charger40 A two-pole, standard | View on Amazon |
| Eaton CHF23030 A · Eaton CH panels · Hardwired charger30 A two-pole, standard | View on Amazon |
A charger for the 14-50 outlet
| Grizzl-E Classic 40A40 A · J1772 · plug-inRugged metal enclosure, built for outdoor use. Can be set to 16, 24, 32 or 40 A inside the unit. Breaker and settings | View on Amazon |
| ChargePoint Home Flex NEMA 14-5040 A · J1772 · plug-inPlugs into an existing 14-50 outlet, no hardwiring. Breaker and settings | View on Amazon |
A 48 A charger for the 60 A circuit
| Wallbox Pulsar Plus 48A48 A · J1772 · hardwiredCompact unit, good for tight garages. Breaker and settings | View on Amazon |
| Tesla Wall Connector48 A · NACS · hardwiredTesla's own unit. Native NACS, hardwire only. Breaker and settings | View on Amazon |
As an Amazon Associate we earn from qualifying purchases.
Common questions
- What breaker does a 14-50 outlet need in an Eaton CH panel?
- A CH250GFT: 50 A, two-pole, with GFCI protection, which section 625.54 of the 2020 and 2023 National Electrical Code requires for a new outlet for EV charging. Wire it with 8 AWG copper wire in conduit or 6 AWG NM cable. It suits a charger set to 40 A.
- What breaker does a 48 A charger need in an Eaton CH panel?
- A CHP260, a standard 60 A two-pole breaker, with 6 AWG copper wire in conduit or 4 AWG NM cable. A charger is a continuous load, so the breaker is rated at 125% of its current. A 48 A charger has to be hardwired, since a 60 A circuit has no common outlet.
- Can I use a BR breaker in a CH panel?
- No. BR breakers are 1 inch per pole and CH breakers 3/4 inch, and each fits only its own panel, though Eaton makes both. The panel's label lists the breakers it accepts.
- Does a hardwired charger need a GFCI breaker?
- Usually not. The GFCI rule in section 625.54 covers outlets, and most hardwired chargers have ground-fault protection built in, as Tesla's Wall Connector manual lists for that unit. Outdoors, section 210.8(F) can call for one on a circuit of 50 A or less, so the electrician and the local inspector have the final word.
Other panels
To size the circuit from the car, see breaker and wire size and the chargers compared.
Part numbers are from Eaton's CH250GFT page, CHN250GF page, CHP260 page and the rest of the maker's catalog. Code references are to the National Electrical Code. Local rules differ, so have a licensed electrician confirm the breaker and wire before work starts. Updated November 13, 2026.