Eaton CH breaker for an EV charger

The breaker
CH250GFT or CHP260
The CH250GFT is a 50 A GFCI breaker for a 40 A charger on a 14-50 outlet. The CHP260 is a standard 60 A breaker for a 48 A charger, hardwired.

These fit Eaton CH panels. The label inside the panel door names the maker and lists the breakers the panel accepts, so check it first. CH breakers are 3/4 inch wide per pole, with a trip flag and tan handles on most. Eaton's BR breakers are wider and do not fit a CH panel.

By charger

A charger may draw 80% of its breaker's rating, so each charger setting needs the breaker below. A charger that plugs into an outlet needs the GFCI version; a hardwired one usually takes the standard version.

Charger set toBreakerand wireCopper wirePlugs into an outletHardwired
16 A20 A12 AWG12 AWG CH220GFT or CHN220GF
a 6-20 outlet
CHF220
24 A30 A10 AWG10 AWG CH230GFT or CHN230GF
a 14-30 or 6-30 outlet
CHF230
32 A40 A8 AWG8 AWG CH240GFT or CHN240GF
a 6-50 or 14-50 outlet on a 40 A circuit
CHF240
40 A50 A8 AWG, or 6 AWG NM cable8 AWG, or 6 AWG NM cable CH250GFT or CHN250GF
a 14-50 or 6-50 outlet
CHF250
48 A60 A6 AWG, or 4 AWG NM cable6 AWG, or 4 AWG NM cable No common outlet; hardwire it CHP260

Every breaker here is two-pole, 120/240 V. Wire sizes are from NEC Table 310.16: the 75°C column for wire in conduit and the 60°C column for NM cable. A long run may need a size larger. The second GFCI number is the plug-on neutral version.

Outlet or hardwired

Before buying

Where to buy

The links search Amazon for each part number. Check that the listing shows the same number before buying.

For a charger that plugs into an outlet

Eaton CH250GFT50 A · Eaton CH panels · 14-50 or 6-50 outlet50 A two-pole GFCI, self-testing, with a pigtail neutral View on Amazon
Eaton CH240GFT40 A · Eaton CH panels · 14-50 or 6-50 outlet, 40 A circuit40 A two-pole GFCI, self-testing, with a pigtail neutral View on Amazon
Eaton CH230GFT30 A · Eaton CH panels · 14-30 or 6-30 outlet30 A two-pole GFCI, self-testing, with a pigtail neutral View on Amazon
Eaton CH220GFT20 A · Eaton CH panels · 6-20 outlet20 A two-pole GFCI, self-testing, with a pigtail neutral View on Amazon

GFCI, for a panel with a plug-on neutral rail

Eaton CHN250GF50 A · Eaton CH panels · 14-50 or 6-50 outlet50 A two-pole GFCI, plug-on neutral View on Amazon
Eaton CHN240GF40 A · Eaton CH panels · 14-50 or 6-50 outlet, 40 A circuit40 A two-pole GFCI, plug-on neutral View on Amazon

For a hardwired charger

Eaton CHP26060 A · Eaton CH panels · Hardwired charger60 A two-pole, standard. Eaton's 60 A CH breaker is the CHP260; the CHF line stops at 50 A. View on Amazon
Eaton CHF25050 A · Eaton CH panels · Hardwired charger50 A two-pole, standard View on Amazon
Eaton CHF24040 A · Eaton CH panels · Hardwired charger40 A two-pole, standard View on Amazon
Eaton CHF23030 A · Eaton CH panels · Hardwired charger30 A two-pole, standard View on Amazon

A charger for the 14-50 outlet

Grizzl-E Classic 40A40 A · J1772 · plug-inRugged metal enclosure, built for outdoor use. Can be set to 16, 24, 32 or 40 A inside the unit. Breaker and settings View on Amazon
ChargePoint Home Flex NEMA 14-5040 A · J1772 · plug-inPlugs into an existing 14-50 outlet, no hardwiring. Breaker and settings View on Amazon

A 48 A charger for the 60 A circuit

Wallbox Pulsar Plus 48A48 A · J1772 · hardwiredCompact unit, good for tight garages. Breaker and settings View on Amazon
Tesla Wall Connector48 A · NACS · hardwiredTesla's own unit. Native NACS, hardwire only. Breaker and settings View on Amazon

As an Amazon Associate we earn from qualifying purchases.

Common questions

What breaker does a 14-50 outlet need in an Eaton CH panel?
A CH250GFT: 50 A, two-pole, with GFCI protection, which section 625.54 of the 2020 and 2023 National Electrical Code requires for a new outlet for EV charging. Wire it with 8 AWG copper wire in conduit or 6 AWG NM cable. It suits a charger set to 40 A.
What breaker does a 48 A charger need in an Eaton CH panel?
A CHP260, a standard 60 A two-pole breaker, with 6 AWG copper wire in conduit or 4 AWG NM cable. A charger is a continuous load, so the breaker is rated at 125% of its current. A 48 A charger has to be hardwired, since a 60 A circuit has no common outlet.
Can I use a BR breaker in a CH panel?
No. BR breakers are 1 inch per pole and CH breakers 3/4 inch, and each fits only its own panel, though Eaton makes both. The panel's label lists the breakers it accepts.
Does a hardwired charger need a GFCI breaker?
Usually not. The GFCI rule in section 625.54 covers outlets, and most hardwired chargers have ground-fault protection built in, as Tesla's Wall Connector manual lists for that unit. Outdoors, section 210.8(F) can call for one on a circuit of 50 A or less, so the electrician and the local inspector have the final word.

Other panels

To size the circuit from the car, see breaker and wire size and the chargers compared.

Part numbers are from Eaton's CH250GFT page, CHN250GF page, CHP260 page and the rest of the maker's catalog. Code references are to the National Electrical Code. Local rules differ, so have a licensed electrician confirm the breaker and wire before work starts. Updated November 13, 2026.