BuyWhatFits

Siemens generator interlock kit

The kit
ECSBPK03, ECSBPK01 or ECSBPK02
The kit depends on the main breaker. The generator breaker is a Q230 for a 30 A generator or a Q250 for a 50 A one.

An interlock is a plate on the panel's cover that lets either the main breaker or the generator breaker be on, never both, so a portable generator can feed the house without sending power back into the utility's lines. Each kit is made for one panel line and one kind of main breaker. The label inside the panel door names the maker and the panel's catalog number, and the main breaker's type is printed on the breaker itself. Siemens home panels take type QP breakers, 1 inch wide per pole; the GFCI version is type QPF. The door label lists the types the panel accepts.

By main breaker

KitMain breakerFits
ECSBPK03MBK150A, MBK200A or MBK225A main breakerSiemens Ultimate and Murray Rock Solid panels, 150 A and up
The generator breaker is a standard type QP, not AFCI, GFCI, three-pole or half-inch; not for 125 A panels with four spaces
ECSBPK01Two-pole main across from the generator breakerSiemens panels and meter combinations with the two breakers opposite
For a main that faces the generator breaker across the panel
ECSBPK02Two- or four-pole main beside the generator breakerSiemens panels and meter combinations with the two breakers side by side
For a main with the generator breaker next to it

The ECSBPK03 is for Siemens Ultimate and Murray Rock Solid panels. For other Siemens panels, ECSBPK01 or ECSBPK02 depends on where the generator breaker sits against the main.

Generator breaker, inlet and cord

The generator breaker is a standard two-pole breaker from the panel's own line, fed backward from the generator. Its size follows the generator's 240 V outlet.

Generator outletUp toBreakerCopper wireInletCord
L14-307,200 WQ230
30 A
10 AWGL14-30 inletL14-30P to L14-30R
14-50 or CS636912,000 WQ250
50 A
8 AWG, or 6 AWG NM cableCS6375 inlet14-50P or CS6364 to CS6365

Watts are the outlet's limit at 240 V; the generator's own running rating may be lower. Wire sizes are from NEC Table 310.16: the 75°C column for wire in conduit and the 60°C column for NM cable.

Before buying

Where to buy

The links search Amazon for each part number. Check that the listing shows the same number before buying.

The interlock kit

Siemens ECSBPK03150 to 225 A · Siemens Ultimate and Murray Rock Solid panels, 150 A and up · Interlock kitMBK150A, MBK200A or MBK225A main breaker. The generator breaker is a standard type QP, not AFCI, GFCI, three-pole or half-inch; not for 125 A panels with four spaces View on Amazon
Siemens ECSBPK01Up to 225 A · Siemens panels and meter combinations with the two breakers opposite · Interlock kitTwo-pole main across from the generator breaker. For a main that faces the generator breaker across the panel View on Amazon
Siemens ECSBPK02Up to 225 A · Siemens panels and meter combinations with the two breakers side by side · Interlock kitTwo- or four-pole main beside the generator breaker. For a main with the generator breaker next to it View on Amazon

The generator breaker

Siemens Q23030 A · Siemens panels for type QP · Generator with an L14-30 outlet30 A two-pole, backfed as the generator breaker; needs a hold-down View on Amazon
Siemens Q25050 A · Siemens panels for type QP · Generator with a 14-50 or CS6369 outlet50 A two-pole, backfed as the generator breaker; needs a hold-down View on Amazon

Inlet and cord

L14-30 power inlet box30 A · Any panel · Outside wallTakes the cord from a generator with an L14-30 outlet View on Amazon
L14-30 generator cord30 A · Any panel · Generator to inletL14-30P plug to L14-30R connector View on Amazon
CS6375 50 amp power inlet box50 A · Any panel · Outside wallTakes the cord from a generator with a 50 A outlet View on Amazon
CS6364 to CS6365 50 amp generator cord50 A · Any panel · Generator to inletFor a generator with a CS6369 outlet View on Amazon
14-50P to CS6365 50 amp generator cord50 A · Any panel · Generator to inletFor a generator with a 14-50 outlet View on Amazon

Other makers' kits

Generator interlock kit for SiemensSee listing · Siemens panels for type QP · Interlock kitPlates from other makers, each for named panel models. Check that the listing names the catalog number on your panel's label View on Amazon

As an Amazon Associate we earn from qualifying purchases.

Common questions

Which generator interlock kit fits a Siemens panel?
It depends on the main breaker: the ECSBPK03 for Siemens Ultimate and Murray Rock Solid panels, 150 A and up (MBK150A, MBK200A or MBK225A main breaker); the ECSBPK01 for Siemens panels and meter combinations with the two breakers opposite (two-pole main across from the generator breaker); the ECSBPK02 for Siemens panels and meter combinations with the two breakers side by side (two- or four-pole main beside the generator breaker). The ECSBPK03 is for Siemens Ultimate and Murray Rock Solid panels. For other Siemens panels, ECSBPK01 or ECSBPK02 depends on where the generator breaker sits against the main. The kit has to be one the panel is listed for.
What is the generator breaker in a Siemens panel?
A Q230 for a generator with an L14-30 outlet, wired with 10 AWG copper wire, or a Q250 for one with a 14-50 or CS6369 outlet, wired with 8 AWG copper wire in conduit or 6 AWG NM cable. It is fed from the generator rather than the panel, so section 408.36(D) of the National Electrical Code requires a hold-down that keeps it from being pulled off.
Is a generator interlock kit up to code?
Yes, when it is listed for the panel. Section 702.5 of the National Electrical Code requires transfer equipment for a generator that feeds a house, so it cannot send power back into the utility's lines, and an interlock does that by keeping the main and generator breakers from being on together. Most places require a permit, and some inspectors accept only the panel maker's kit.
Can a portable generator run an EV charger through an interlock?
Rarely. A charger set to 40 A draws 9,600 W, more than an L14-30 generator outlet supplies (7,200 W), and most of what a 50 A outlet supplies (12,000 W) before the house's own loads. Switch the charger's breaker off while on generator power, or turn the charger's current down if the generator has room to spare.

Other panels

Kit numbers are from Siemens' load center accessory guide, SupplyHouse's ECSBPK03 listing, Dale Electric's ECSBPK01 and ECSBPK02 listings. Code references are to the National Electrical Code. Local rules differ, so have a licensed electrician confirm the kit, breaker and wire before work starts. Updated November 13, 2026.