Square D Homeline generator interlock kit

The kit
HOMCRBGK1C or HOMCGK2C
The kit depends on the main breaker. The generator breaker is a HOM230 for a 30 A generator or a HOM250 for a 50 A one.

An interlock is a plate on the panel's cover that lets either the main breaker or the generator breaker be on, never both, so a portable generator can feed the house without sending power back into the utility's lines. Each kit is made for one panel line and one kind of main breaker. The label inside the panel door names the maker and the panel's catalog number, and the main breaker's type is printed on the breaker itself. Homeline breakers are 1 inch wide per pole, so a two-pole one is 2 inches. Square D's other line, QO, is narrower, and the two do not interchange.

By main breaker

KitMain breakerFits
HOMCRBGK1CQOM1 main breakerHomeline panels of 100 A and 125 A
Series S panels, indoor or outdoor
HOMCGK2CQOM2 main breakerHomeline panels of 150 A to 225 A
Series S indoor or Series S1 outdoor panels

Square D's FAQ lists no kit for its 60-space Homeline panels.

Generator breaker, inlet and cord

The generator breaker is a standard two-pole breaker from the panel's own line, fed backward from the generator. Its size follows the generator's 240 V outlet.

Generator outletUp toBreakerCopper wireInletCord
L14-307,200 WHOM230
30 A
10 AWGL14-30 inletL14-30P to L14-30R
14-50 or CS636912,000 WHOM250
50 A
8 AWG, or 6 AWG NM cableCS6375 inlet14-50P or CS6364 to CS6365

Watts are the outlet's limit at 240 V; the generator's own running rating may be lower. Wire sizes are from NEC Table 310.16: the 75°C column for wire in conduit and the 60°C column for NM cable.

Before buying

Where to buy

The links search Amazon for each part number. Check that the listing shows the same number before buying.

The interlock kit

Square D HOMCRBGK1C100 to 125 A · Homeline panels of 100 A and 125 A · Interlock kitQOM1 main breaker. Series S panels, indoor or outdoor View on Amazon
Square D HOMCGK2C150 to 225 A · Homeline panels of 150 A to 225 A · Interlock kitQOM2 main breaker. Series S indoor or Series S1 outdoor panels View on Amazon

The generator breaker

Square D HOM23030 A · Homeline panels · Generator with an L14-30 outlet30 A two-pole, backfed as the generator breaker; needs a hold-down View on Amazon
Square D HOM25050 A · Homeline panels · Generator with a 14-50 or CS6369 outlet50 A two-pole, backfed as the generator breaker; needs a hold-down View on Amazon

Inlet and cord

L14-30 power inlet box30 A · Any panel · Outside wallTakes the cord from a generator with an L14-30 outlet View on Amazon
L14-30 generator cord30 A · Any panel · Generator to inletL14-30P plug to L14-30R connector View on Amazon
CS6375 50 amp power inlet box50 A · Any panel · Outside wallTakes the cord from a generator with a 50 A outlet View on Amazon
CS6364 to CS6365 50 amp generator cord50 A · Any panel · Generator to inletFor a generator with a CS6369 outlet View on Amazon
14-50P to CS6365 50 amp generator cord50 A · Any panel · Generator to inletFor a generator with a 14-50 outlet View on Amazon

Other makers' kits

Generator interlock kit for Square D HomelineSee listing · Homeline panels · Interlock kitPlates from other makers, each for named panel models. Check that the listing names the catalog number on your panel's label View on Amazon

As an Amazon Associate we earn from qualifying purchases.

Common questions

Which generator interlock kit fits a Square D Homeline panel?
It depends on the main breaker: the HOMCRBGK1C for Homeline panels of 100 A and 125 A (QOM1 main breaker); the HOMCGK2C for Homeline panels of 150 A to 225 A (QOM2 main breaker). Square D's FAQ lists no kit for its 60-space Homeline panels. The kit has to be one the panel is listed for.
What is the generator breaker in a Square D Homeline panel?
A HOM230 for a generator with an L14-30 outlet, wired with 10 AWG copper wire, or a HOM250 for one with a 14-50 or CS6369 outlet, wired with 8 AWG copper wire in conduit or 6 AWG NM cable. It is fed from the generator rather than the panel, so section 408.36(D) of the National Electrical Code requires a hold-down that keeps it from being pulled off.
Is a generator interlock kit up to code?
Yes, when it is listed for the panel. Section 702.5 of the National Electrical Code requires transfer equipment for a generator that feeds a house, so it cannot send power back into the utility's lines, and an interlock does that by keeping the main and generator breakers from being on together. Most places require a permit, and some inspectors accept only the panel maker's kit.
Can a portable generator run an EV charger through an interlock?
Rarely. A charger set to 40 A draws 9,600 W, more than an L14-30 generator outlet supplies (7,200 W), and most of what a 50 A outlet supplies (12,000 W) before the house's own loads. Switch the charger's breaker off while on generator power, or turn the charger's current down if the generator has room to spare.

Other panels

Kit numbers are from Square D's Homeline interlock FAQ. Code references are to the National Electrical Code. Local rules differ, so have a licensed electrician confirm the kit, breaker and wire before work starts. Updated November 13, 2026.