Siemens breaker for an EV charger
These fit Siemens panels for type QP. The label inside the panel door names the maker and lists the breakers the panel accepts, so check it first. Siemens home panels take type QP breakers, 1 inch wide per pole; the GFCI version is type QPF. The door label lists the types the panel accepts.
By charger
A charger may draw 80% of its breaker's rating, so each charger setting needs the breaker below. A charger that plugs into an outlet needs the GFCI version; a hardwired one usually takes the standard version.
| Charger set to | Breakerand wire | Plugs into an outlet | Hardwired |
|---|---|---|---|
| 16 A | 20 A12 AWG | QF220A a 6-20 outlet |
Q220 |
| 24 A | 30 A10 AWG | QF230A a 14-30 or 6-30 outlet |
Q230 |
| 32 A | 40 A8 AWG | QF240A a 6-50 or 14-50 outlet on a 40 A circuit |
Q240 |
| 40 A | 50 A8 AWG, or 6 AWG NM cable | QF250A a 14-50 or 6-50 outlet |
Q250 |
| 48 A | 60 A6 AWG, or 4 AWG NM cable | No common outlet; hardwire it | Q260 |
Every breaker here is two-pole, 120/240 V. Wire sizes are from NEC Table 310.16: the 75°C column for wire in conduit and the 60°C column for NM cable. A long run may need a size larger.
Outlet or hardwired
- An outlet needs GFCI. Section 625.54 of the 2020 and 2023 code requires ground-fault protection on any outlet installed for EV charging, and at 240 V that means a GFCI breaker. The charger's own protection and the breaker's can trip each other; the outlet or hardwired guide covers that trade.
- The pigtail. The QF250A has a coiled white wire that goes to the panel's neutral bar, even for a 6-50 outlet, which has no neutral wire of its own; the breaker's electronics need it.
- Hardwired. The outlet rule does not apply, and most hardwired chargers have ground-fault protection built in, so the standard breaker is usual. Tesla's manual says the Wall Connector needs no additional GFCI. Outdoors, section 210.8(F) can call for GFCI on a circuit of 50 A or less.
- 48 A needs hardwiring. It takes a 60 A breaker, and a 60 A circuit has no common outlet. Only a car that accepts more than 40 A gains from it; see 40 A or 48 A.
Before buying
- Two spaces. A two-pole breaker takes two spaces next to each other in the panel.
- Room on the service. A 50 A or 60 A circuit can overload a small service. The 100 A panel guide covers the load calculation.
- Match the label. Use a breaker type the panel's label lists. One from another line can look like it fits without being listed for that panel.
- A permit. Most places require a permit for a new circuit, and many require a licensed electrician to do the work.
- Generator backup. The Siemens generator interlock page has the kit that lets a portable generator feed this panel, with its breaker, inlet and cord.
Where to buy
The links search Amazon for each part number. Check that the listing shows the same number before buying.
For a charger that plugs into an outlet
| Siemens QF250A50 A · Siemens panels for type QP · 14-50 or 6-50 outlet50 A two-pole GFCI, Class A, 5 mA, with a pigtail neutral | View on Amazon |
| Siemens QF240A40 A · Siemens panels for type QP · 14-50 or 6-50 outlet, 40 A circuit40 A two-pole GFCI, Class A, 5 mA, with a pigtail neutral | View on Amazon |
| Siemens QF230A30 A · Siemens panels for type QP · 14-30 or 6-30 outlet30 A two-pole GFCI, Class A, 5 mA, with a pigtail neutral. Siemens also sells a 30 A two-pole GFCI as the Q230GF. | View on Amazon |
| Siemens QF220A20 A · Siemens panels for type QP · 6-20 outlet20 A two-pole GFCI, Class A, 5 mA, with a pigtail neutral | View on Amazon |
For a hardwired charger
| Siemens Q26060 A · Siemens panels for type QP · Hardwired charger60 A two-pole, standard | View on Amazon |
| Siemens Q25050 A · Siemens panels for type QP · Hardwired charger50 A two-pole, standard | View on Amazon |
| Siemens Q24040 A · Siemens panels for type QP · Hardwired charger40 A two-pole, standard | View on Amazon |
| Siemens Q23030 A · Siemens panels for type QP · Hardwired charger30 A two-pole, standard | View on Amazon |
A charger for the 14-50 outlet
| Grizzl-E Classic 40A40 A · J1772 · plug-inRugged metal enclosure, built for outdoor use. Can be set to 16, 24, 32 or 40 A inside the unit. Breaker and settings | View on Amazon |
| ChargePoint Home Flex NEMA 14-5040 A · J1772 · plug-inPlugs into an existing 14-50 outlet, no hardwiring. Breaker and settings | View on Amazon |
A 48 A charger for the 60 A circuit
| Wallbox Pulsar Plus 48A48 A · J1772 · hardwiredCompact unit, good for tight garages. Breaker and settings | View on Amazon |
| Tesla Wall Connector48 A · NACS · hardwiredTesla's own unit. Native NACS, hardwire only. Breaker and settings | View on Amazon |
As an Amazon Associate we earn from qualifying purchases.
Common questions
- What breaker does a 14-50 outlet need in a Siemens panel?
- A QF250A: 50 A, two-pole, with GFCI protection, which section 625.54 of the 2020 and 2023 National Electrical Code requires for a new outlet for EV charging. Wire it with 8 AWG copper wire in conduit or 6 AWG NM cable. It suits a charger set to 40 A.
- What breaker does a 48 A charger need in a Siemens panel?
- A Q260, a standard 60 A two-pole breaker, with 6 AWG copper wire in conduit or 4 AWG NM cable. A charger is a continuous load, so the breaker is rated at 125% of its current. A 48 A charger has to be hardwired, since a 60 A circuit has no common outlet.
- Which Siemens panels take these breakers?
- Siemens load centers whose label lists type QP breakers, which covers most Siemens home panels. The GFCI breakers are type QPF and fit the same spaces.
- Does a hardwired charger need a GFCI breaker?
- Usually not. The GFCI rule in section 625.54 covers outlets, and most hardwired chargers have ground-fault protection built in, as Tesla's Wall Connector manual lists for that unit. Outdoors, section 210.8(F) can call for one on a circuit of 50 A or less, so the electrician and the local inspector have the final word.
Other panels
To size the circuit from the car, see breaker and wire size and the chargers compared.
Part numbers are from Siemens' QF250A page, Q250 page and the rest of the maker's catalog. Code references are to the National Electrical Code. Local rules differ, so have a licensed electrician confirm the breaker and wire before work starts. Updated November 13, 2026.