Square D Homeline breaker for an EV charger

The breaker
HOM250GFI or HOM260
The HOM250GFI is a 50 A GFCI breaker for a 40 A charger on a 14-50 outlet. The HOM260 is a standard 60 A breaker for a 48 A charger, hardwired.

These fit Homeline panels. The label inside the panel door names the maker and lists the breakers the panel accepts, so check it first. Homeline breakers are 1 inch wide per pole, so a two-pole one is 2 inches. Square D's other line, QO, is narrower, and the two do not interchange.

By charger

A charger may draw 80% of its breaker's rating, so each charger setting needs the breaker below. A charger that plugs into an outlet needs the GFCI version; a hardwired one usually takes the standard version.

Charger set toBreakerand wireCopper wirePlugs into an outletHardwired
16 A20 A12 AWG12 AWG HOM220GFI
a 6-20 outlet
HOM220
24 A30 A10 AWG10 AWG HOM230GFI
a 14-30 or 6-30 outlet
HOM230
32 A40 A8 AWG8 AWG HOM240GFI
a 6-50 or 14-50 outlet on a 40 A circuit
HOM240
40 A50 A8 AWG, or 6 AWG NM cable8 AWG, or 6 AWG NM cable HOM250GFI
a 14-50 or 6-50 outlet
HOM250
48 A60 A6 AWG, or 4 AWG NM cable6 AWG, or 4 AWG NM cable No common outlet; hardwire it HOM260

Every breaker here is two-pole, 120/240 V. Wire sizes are from NEC Table 310.16: the 75°C column for wire in conduit and the 60°C column for NM cable. A long run may need a size larger.

Outlet or hardwired

Before buying

Where to buy

The links search Amazon for each part number. Check that the listing shows the same number before buying.

For a charger that plugs into an outlet

Square D HOM250GFI50 A · Homeline panels · 14-50 or 6-50 outlet50 A two-pole GFCI, Class A, 6 mA, with a pigtail neutral View on Amazon
Square D HOM240GFI40 A · Homeline panels · 14-50 or 6-50 outlet, 40 A circuit40 A two-pole GFCI, Class A, 6 mA, with a pigtail neutral View on Amazon
Square D HOM230GFI30 A · Homeline panels · 14-30 or 6-30 outlet30 A two-pole GFCI, Class A, 6 mA, with a pigtail neutral View on Amazon
Square D HOM220GFI20 A · Homeline panels · 6-20 outlet20 A two-pole GFCI, Class A, 6 mA, with a pigtail neutral View on Amazon

For a hardwired charger

Square D HOM26060 A · Homeline panels · Hardwired charger60 A two-pole, standard View on Amazon
Square D HOM25050 A · Homeline panels · Hardwired charger50 A two-pole, standard View on Amazon
Square D HOM24040 A · Homeline panels · Hardwired charger40 A two-pole, standard View on Amazon
Square D HOM23030 A · Homeline panels · Hardwired charger30 A two-pole, standard View on Amazon

A charger for the 14-50 outlet

Grizzl-E Classic 40A40 A · J1772 · plug-inRugged metal enclosure, built for outdoor use. Can be set to 16, 24, 32 or 40 A inside the unit. Breaker and settings View on Amazon
ChargePoint Home Flex NEMA 14-5040 A · J1772 · plug-inPlugs into an existing 14-50 outlet, no hardwiring. Breaker and settings View on Amazon

A 48 A charger for the 60 A circuit

Wallbox Pulsar Plus 48A48 A · J1772 · hardwiredCompact unit, good for tight garages. Breaker and settings View on Amazon
Tesla Wall Connector48 A · NACS · hardwiredTesla's own unit. Native NACS, hardwire only. Breaker and settings View on Amazon

As an Amazon Associate we earn from qualifying purchases.

Common questions

What breaker does a 14-50 outlet need in a Square D Homeline panel?
A HOM250GFI: 50 A, two-pole, with GFCI protection, which section 625.54 of the 2020 and 2023 National Electrical Code requires for a new outlet for EV charging. Wire it with 8 AWG copper wire in conduit or 6 AWG NM cable. It suits a charger set to 40 A.
What breaker does a 48 A charger need in a Square D Homeline panel?
A HOM260, a standard 60 A two-pole breaker, with 6 AWG copper wire in conduit or 4 AWG NM cable. A charger is a continuous load, so the breaker is rated at 125% of its current. A 48 A charger has to be hardwired, since a 60 A circuit has no common outlet.
Can I use a QO breaker in a Homeline panel?
No. QO breakers are 3/4 inch per pole and Homeline breakers 1 inch, and each fits only its own panel, though Square D makes both. The panel's label lists the breakers it accepts.
Does a hardwired charger need a GFCI breaker?
Usually not. The GFCI rule in section 625.54 covers outlets, and most hardwired chargers have ground-fault protection built in, as Tesla's Wall Connector manual lists for that unit. Outdoors, section 210.8(F) can call for one on a circuit of 50 A or less, so the electrician and the local inspector have the final word.

Other panels

To size the circuit from the car, see breaker and wire size and the chargers compared.

Part numbers are from Square D's HOM250GFI page, HOM260 page and the rest of the maker's catalog. Code references are to the National Electrical Code. Local rules differ, so have a licensed electrician confirm the breaker and wire before work starts. Updated November 13, 2026.