Eaton BR breaker for an EV charger

The breaker
GFTCB250 or BR260
The GFTCB250 is a 50 A GFCI breaker for a 40 A charger on a 14-50 outlet. The BR260 is a standard 60 A breaker for a 48 A charger, hardwired.

These fit Eaton BR panels. The label inside the panel door names the maker and lists the breakers the panel accepts, so check it first. BR breakers are 1 inch wide per pole. Eaton's other line, CH, is narrower, and the two do not interchange. An older panel may carry the Cutler-Hammer name, which Eaton owns.

By charger

A charger may draw 80% of its breaker's rating, so each charger setting needs the breaker below. A charger that plugs into an outlet needs the GFCI version; a hardwired one usually takes the standard version.

Charger set toBreakerand wireCopper wirePlugs into an outletHardwired
16 A20 A12 AWG12 AWG GFTCB220 or BRN220GF
a 6-20 outlet
BR220
24 A30 A10 AWG10 AWG GFTCB230 or BRN230GF
a 14-30 or 6-30 outlet
BR230
32 A40 A8 AWG8 AWG GFTCB240 or BRN240GF
a 6-50 or 14-50 outlet on a 40 A circuit
BR240
40 A50 A8 AWG, or 6 AWG NM cable8 AWG, or 6 AWG NM cable GFTCB250 or BRN250GF
a 14-50 or 6-50 outlet
BR250
48 A60 A6 AWG, or 4 AWG NM cable6 AWG, or 4 AWG NM cable No common outlet; hardwire it BR260

Every breaker here is two-pole, 120/240 V. Wire sizes are from NEC Table 310.16: the 75°C column for wire in conduit and the 60°C column for NM cable. A long run may need a size larger. The second GFCI number is the plug-on neutral version.

Outlet or hardwired

Before buying

Where to buy

The links search Amazon for each part number. Check that the listing shows the same number before buying.

For a charger that plugs into an outlet

Eaton GFTCB25050 A · Eaton BR panels · 14-50 or 6-50 outlet50 A two-pole GFCI, self-testing, with a pigtail neutral View on Amazon
Eaton GFTCB24040 A · Eaton BR panels · 14-50 or 6-50 outlet, 40 A circuit40 A two-pole GFCI, self-testing, with a pigtail neutral View on Amazon
Eaton GFTCB23030 A · Eaton BR panels · 14-30 or 6-30 outlet30 A two-pole GFCI, self-testing, with a pigtail neutral View on Amazon
Eaton GFTCB22020 A · Eaton BR panels · 6-20 outlet20 A two-pole GFCI, self-testing, with a pigtail neutral View on Amazon

GFCI, for a panel with a plug-on neutral rail

Eaton BRN250GF50 A · Eaton BR panels · 14-50 or 6-50 outlet50 A two-pole GFCI, plug-on neutral View on Amazon
Eaton BRN240GF40 A · Eaton BR panels · 14-50 or 6-50 outlet, 40 A circuit40 A two-pole GFCI, plug-on neutral View on Amazon

For a hardwired charger

Eaton BR26060 A · Eaton BR panels · Hardwired charger60 A two-pole, standard View on Amazon
Eaton BR25050 A · Eaton BR panels · Hardwired charger50 A two-pole, standard View on Amazon
Eaton BR24040 A · Eaton BR panels · Hardwired charger40 A two-pole, standard View on Amazon
Eaton BR23030 A · Eaton BR panels · Hardwired charger30 A two-pole, standard View on Amazon

A charger for the 14-50 outlet

Grizzl-E Classic 40A40 A · J1772 · plug-inRugged metal enclosure, built for outdoor use. Can be set to 16, 24, 32 or 40 A inside the unit. Breaker and settings View on Amazon
ChargePoint Home Flex NEMA 14-5040 A · J1772 · plug-inPlugs into an existing 14-50 outlet, no hardwiring. Breaker and settings View on Amazon

A 48 A charger for the 60 A circuit

Wallbox Pulsar Plus 48A48 A · J1772 · hardwiredCompact unit, good for tight garages. Breaker and settings View on Amazon
Tesla Wall Connector48 A · NACS · hardwiredTesla's own unit. Native NACS, hardwire only. Breaker and settings View on Amazon

As an Amazon Associate we earn from qualifying purchases.

Common questions

What breaker does a 14-50 outlet need in an Eaton BR panel?
A GFTCB250: 50 A, two-pole, with GFCI protection, which section 625.54 of the 2020 and 2023 National Electrical Code requires for a new outlet for EV charging. Wire it with 8 AWG copper wire in conduit or 6 AWG NM cable. It suits a charger set to 40 A.
What breaker does a 48 A charger need in an Eaton BR panel?
A BR260, a standard 60 A two-pole breaker, with 6 AWG copper wire in conduit or 4 AWG NM cable. A charger is a continuous load, so the breaker is rated at 125% of its current. A 48 A charger has to be hardwired, since a 60 A circuit has no common outlet.
Can I use a CH breaker in a BR panel?
No. CH breakers are 3/4 inch per pole and BR breakers 1 inch, and each fits only its own panel, though Eaton makes both. The panel's label lists the breakers it accepts.
Does a hardwired charger need a GFCI breaker?
Usually not. The GFCI rule in section 625.54 covers outlets, and most hardwired chargers have ground-fault protection built in, as Tesla's Wall Connector manual lists for that unit. Outdoors, section 210.8(F) can call for one on a circuit of 50 A or less, so the electrician and the local inspector have the final word.

Other panels

To size the circuit from the car, see breaker and wire size and the chargers compared.

Part numbers are from Eaton's GFTCB250 page, BRN250GF page, BR260 page and the rest of the maker's catalog. Code references are to the National Electrical Code. Local rules differ, so have a licensed electrician confirm the breaker and wire before work starts. Updated November 13, 2026.